High temperature teflon calbe KF

Applications:

This product is suitable for AC  rated voltage 450/750V electrical instru mentation and automatic control system  cable transmission line,with  oil,water,abrasion,acid and a  varity of corrosive gas,anti-aging,non-combustion and excellent performance for  metallurgy,electric power,petrochemical and other industries.

Technical date:

AC rated voltage: U0/U  450/750KV
Maximum operating  temperature:poly FEP(F46) insulation does not exceed 200℃
Minimum ambient temperature:PVC  sheath:Fixed laying -40℃,non-fixed  laying -15℃;Fluorine plastic sheath: Fixed  laying -60℃,non-fixed laying -20℃
Laying of cable installation  temperature should not be less than 0℃
Cable bending  radius:Cablebengding radius:non-armored cable a minimum of 6 times the cable  diameter;Fluoride plastic insulated and sheathed cable with a minimum of 8  times the cable diameter
Executive Standard:  GJB773A/11A-2000

Fluorine plastic high temperature CONTROL cables

Basic Model and name
typeProduct Name
SKFFFluorine 46 (FEP) insulated and sheathed control cable
KFFPFluorine 46 (FEP) insulated and sheathed copper braided shield control cable
KFFRPFluorine 46 (FEP) insulated and sheathed copper braided shield flexible control cable
KFFP1Fluorine 46 (FEP) insulated and tinned copper braid sheath control cable
KFFRP2Fluorine 46 (FEP) insulated and sheathed copper shield around the control cable package
KFVFluorine 46 (FEP)  insulated PVC sheathed control cable
KFVRFluorine 46 (FEP) insulated PVC sheathed control cable
KFVRPFluorine 46 (FEP) insulated copper wire braided shield PVC sheathed control cable
KFGR(YGC-KF46R)Fluorine 46 (FEP) silicone rubber insulated control cable sheath
KFGPR(YGC-KF46RP)Fluorine 46 (FEP) silicone rubber insulated wire braided shield sheath control cable
ConductorInsulationJacketElectrical
     Properties
Sectional
     Area    mm²
Conductor
     Construction
     NO.XΦmm
Insulation
     Thickness
     mm
Outer
     Diameter
     mm
Jacket
     Thickness
     mm
Average
     Diameter
     mm
Max.Conductor
     Resistance    DC 20℃
     Ω/km
2x0.3519/0.160.251.30.253.149.5
3x0.3519/0.160.251.30.253.249.5
4x0.3519/0.160.251.30.253.6549.5
5x0.3519/0.160.251.30.34.149.5
6x0.3519/0.160.251.30.34.549.5
7x0.3519/0.160.251.30.34.549.5
2x0.519/0.180.251.40.253.336
3x0.519/0.180.251.40.253.436
4x0.519/0.180.251.40.3436
5x0.519/0.180.251.40.34.436
6x0.519/0.180.251.40.34.836
7x0.519/0.180.251.40.34.836
2x0.7519/0.230.251.70.3422.7
3x0.7519/0.230.251.70.3422.7
4x0.7519/0.230.251.70.34.722.7
5x0.7519/0.230.251.70.355.322.7
6x0.7519/0.230.251.70.355.822.7
7x0.7519/0.230.251.70.355.822.7
2x119/0.260.251.80.34.219
3x119/0.260.251.80.354.319
4x119/0.260.251.80.355.119
5x119/0.260.251.80.355.619
6x119/0.260.251.80.46.219
7x119/0.260.251.80.46.219
Code names and meanings
NameCodeMeaning of codes
series of codesKControl cable
Insulation materialsFPoly FEP(F46)maximum operating temperature of 200℃
Soluble Teflon (PFA)maximum operating temperature of 260℃
Sheath materialFPoly FEP(F46)maximum operating temperature of 200℃
Soluble Teflon (PFA)maximum operating temperature of 260℃
VPolyvinyl chloride (PVC)
GSilicone rubber
Flame retardant propertiesZR(V)Flame retardant PVC(Three kinds of 70℃、90℃、105℃)
The main technical indicators
Finished cable conductor DC resistance (in accordance with the provisions of GB3956)
20℃when the insulation resistance of not less than 500MΩ/KM
Finished cable communication 50HZ3.0KV/5min withstand voltage test without breakdown